Schneider Electric LC1D18 Contactor 24VDC Coil
Brand: Schneider Electric | Model: LC1D18 | Condition: Used | NEO SKU: 12064-6
Original price was: $24.12.$19.86Current price is: $19.86.
2 in stock
Free Shipping on orders over $50.
*(Domestic only)
Need it fast? Next Day Air available at check out.
Same Day Handling on orders prior to 2pm Eastern Monday – Friday
2 in stock
NEO SKU: 12064-6 | Category: Definite Purpose Contactors
Product Details for Used: Schneider Electric LC1D18 Contactor 24VDC Coil
Only logged in customers who have purchased this product may leave a review.
Schneider Electric LC1D18 Contactor 24VDC Coil
Specifications:
SKU: 12064-6
Condition: Used
Brand: Schneider Electric
Model: LC1D18
Description: Contactor 24VDC Coil
*Actual product may vary from images.*
Additional MFG Notes on Schneider Electric LC1D18 Contactor 24VDC Coil:
IEC contactor, TeSys Deca, nonreversing, 18A, 10HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VDC coil, open
Main
Range of Product: TeSys Deca
Product or Component Type: Contactor
Device short name: LC1D
contactor application: Motor control
Resistive load: utilisation category
AC-4
AC-1
AC-3
AC-3e
Poles description: 3P
[Ue] rated operational voltage:
Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current:
18 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
32 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
18 A 140 °F (60 °C)) <= 440 V AC AC-3e power circuit
[Uc] control circuit voltage: 24 V DC
Complementary
Motor power kW:
4 kW 220...230 V AC 50/60 Hz AC-3)
7.5 kW 380...400 V AC 50/60 Hz AC-3)
9 kW 415...440 V AC 50/60 Hz AC-3)
10 kW 500 V AC 50/60 Hz AC-3)
10 kW 660...690 V AC 50/60 Hz AC-3)
4 kW 400 V AC 50/60 Hz AC-4)
4 kW 220...230 V AC 50/60 Hz AC-3e)
7.5 kW 380...400 V AC 50/60 Hz AC-3e)
9 kW 415...440 V AC 50/60 Hz AC-3e)
10 kW 500 V AC 50/60 Hz AC-3e)
10 kW 660...690 V AC 50/60 Hz AC-3e)
Maximum Horse Power Rating:
1 hp 115 V at AC 50/60 Hz for 1 phase
3 hp 230/240 V at AC 50/60 Hz for 1 phase
5 hp 200/208 V at AC 50/60 Hz for 3 phase
5 hp 230/240 V at AC 50/60 Hz for 3 phase
10 hp 460/480 V at AC 50/60 Hz for 3 phase
15 hp 575/600 V at AC 50/60 Hz for 3 phase
Compatibility code: LC1D
Pole contact composition: 3 NO
Contact compatibility: M4
Protective cover: With
[Ith] conventional free air thermal current
10 A 140 °F (60 °C) signalling circuit
32 A 140 °F (60 °C) power circuit
Irms rated making capacity
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1
300 A 440 V power circuit IEC 60947
Rated breaking capacity:
300 A 440 V power circuit IEC 60947
[Icw] rated short-time withstand current
145 A 104 °F (40 °C) - 10 s power circuit
240 A 104 °F (40 °C) - 1 s power circuit
40 A 104 °F (40 °C) - 10 min power circuit
84 A 104 °F (40 °C) - 1 min power circuit
100 A - 1 s signalling circuit
120 A - 500 ms signalling circuit
140 A - 100 ms signalling circuit
Associated fuse rating:
10 A gG signalling circuit IEC 60947-5-1
50 A gG <= 690 V type 1 power circuit
35 A gG <= 690 V type 2 power circuit
Average impedance:
2.5 mOhm - Ith 32 A 50 Hz power circuit
Power dissipation per pole:
2.5 W AC-1
0.8 W AC-3
0.8 W AC-3e
[Ui] rated insulation voltage:
Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage category: III
Pollution degree: 3
[Uimp] rated impulse withstand voltage: 6 kV IEC 60947
Safety reliability level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability: 30 Mcycles
Electrical durability:
1.65 Mcycles 18 A AC-3 <= 440 V
1 Mcycles 32 A AC-1 <= 440 V
1.65 Mcycles 18 A AC-3e <= 440 V
Control circuit type: DC standard
Coil technology: With integral suppression device
Control circuit voltage limits:
0.1...0.25 Uc -40…158 °F (-40…70 °C) drop-out DC
0.7...1.25 Uc -40…140 °F (-40…60 °C) operational DC
1...1.25 Uc 140…158 °F (60…70 °C) operational DC
Inrush power in W: 5.4 W 68 °F (20 °C))
Hold-in power consumption in W: 5.4 W 68 °F (20 °C)
Operating time:
53.55...72.45 ms closing
16...24 ms opening
Time constant: 28 ms
Maximum operating rate: 3600 cyc/h 140 °F (60 °C)
Connections - terminals:
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible without cable end
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible without cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible with cable end
Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible with cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) solid without cable end
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) solid without cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1.5…6 mm²) flexible without cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²) flexible without cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…6 mm²) flexible with cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible with cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1.5…6 mm²) solid without cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1.5…6 mm²) solid without cable end
Tightening torque:
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition: 1 NO + 1 NC
Auxiliary contacts type: Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency: 25...400 Hz
Minimum switching voltage: 17 V signalling circuit
Minimum switching current: 5 mA signalling circuit
Insulation resistance: > 10 MOhm signalling circuit
Non-overlap time:
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support: Plate
Rail
Environment
Standards:
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1
Product Certifications:
LROS (Lloyds register of shipping)
DNV
GL
RINA
BV
CCC
UL
CSA
GOST
UKCA
IP degree of protection: IP20 front face IEC 60529
Protective treatment: THIEC 60068-2-30
Climatic withstand:
IACS E10 exposure to damp heat
IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device:
-40…140 °F (-40…60 °C)
140…158 °F (60…70 °C) with derating
Operating altitude: 0…9842.52 ft (0…3000 m)
Fire resistance: 1562 °F (850 °C) IEC 60695-2-1
Flame retardance: V1 conforming to UL 94
Mechanical robustness:
Vibrations contactor open 2 Gn, 5…300 Hz)
Vibrations contactor closed 4 Gn, 5…300 Hz)
Shocks contactor open 10 Gn for 11 ms)
Shocks contactor closed 15 Gn for 11 ms)
Height: 3.03 in (77 mm)
Width: 1.77 in (45 mm)
Depth: 3.74 in (95 mm)
Net Weight: 1.08 lb(US) (0.49 kg)
Category: 22355-CTR,TESYS D,OPEN,9-38A DC
GTIN: 3389110354775
NEO Surplus is not an authorized distributor, representative, reseller, or affiliated with Schneider Electric or any manufacturer, brand, or product. Items being sold are not covered under any manufacturer warranty. All trademarks, brand names and brands appearing herein are the property of their respective owners.
We do our best to get all the information in this listing correct. If you see an error or have any questions, please contact us.
Additional information
Weight | 3 lbs |
---|---|
Dimensions | 8 × 8 × 7 in |
Brand | Schneider Electric |
Model | LC1D18 |
Condition | Used |
MFG Notes | 10HP at 480VAC, 18A, 24VDC coil, 3 NO, 3 phase, 5…300 Hz) Vibrations contactor closed 4 Gn, 9-38A DC GTIN: 3389110354775, IEC contactor, nonreversing, OPEN, TESYS D, TeSys Deca, up to 100kA SCCR |
Related Products
FAQ’s
Looking for a replacement Schneider Electric LC1D18 with fast shipping?
NEO Surplus will ship in stock items the same day if purchased by 2pm ET, Monday – Friday.
Can I ship using my carrier account?
Do you offer Blind Shipping?
Other Questions?
Contact us if you have more questions.NEO Surplus is not an authorized distributor, representative, reseller, or affiliated with Schneider Electric or any manufacturer, brand, or product. Items being sold are not covered under any manufacturer warranty. All trademarks, brand names and brands appearing herein are the property of their respective owners.
NEO Surplus buys surplus MRO items and then resells them on the secondary parts markets.
We do our best to get all the information in this listing correct. If you have any questions or see an error, please contact us.
Reviews
There are no reviews yet.